Permit Number: T16CM03082
Parcel: 12411021E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM03082
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/16/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The specification for the automatic faucet does not indicate that the faucet will deliver a maximum of 0.25 gallons per cycle and operate for a minimum of 10 seconds per cycle . [Initial comment: Provide the specifications for the temperature mixing valve shown in detail 5/P-610. Verify that the water temperature in the public lavatories will be limited to 110 degrees Fahrenheit. Reference: Section C404.3, IECC 2012.]
Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
05/16/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed