Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM03071
Parcel: 123080490

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T16CM03071
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2016 ANDREW CONNOR ZONING REVIEW Needs Review COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing a 1' set from property line for addition to existing accessory structure.
04/28/2016 ANDREW CONNOR NPPO REVIEW Passed
12/07/2016 KROBLES1 ENGINEERING REVIEW Needs Review
12/07/2016 KROBLES1 BUILDING-RESIDENTIAL REVIEW Needs Review