Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM03020
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The proposed backflow preventer (Watts LF7) is listed to ASSE 1024, not ASSE 1022. [Initial comment: Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.] |
| 08/03/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The location of the reduced pressure backflow preventer has not been shown. [Initial comment: Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Install the backflow prevention assembly in a location accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf] |
| 08/04/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/04/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The energy code compliance calculations for the additions to the building envelope have not been provided by the architect. [Initial comment: Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.3, C101.5, C103.2, and C303, International Energy Conservation Code 2012.] |
| 08/17/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/19/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Catalina Care - Expansion T16CM03020 Building Plan (2nd Review) TRANSMITTAL DATE: August 24, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The building plans have been reviewed for compliance with development package DP16-0053 and it appears that the plans meet the requirements. But until the development package has been approved Zoning cannot approve the building plans. 3. The development package sheets provide in the building plan have not been approved. Either the development package sheets need to be the approved sheets, marked as for reference only or removed from the building plans. 4. Ensure that all details shown sheets A-002 & A-003 match what is shown on development package DP16-0053 or they are marked for reference only. 5. Until the building plan has been approved by all PDSD agencies Zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 08/30/2016 | ARUIZ1 | ENGINEERING | REVIEW | Needs Review |