Permit Number: T16CM03008
Parcel: 12105004A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM03008
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2016 ANDREW CONNOR ZONING REVIEW Approved
06/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The sequence of operation for exhaust fans EF-9, 10, 12, and 14 still need to be addressed. [Initial comment: Revise the sequence of operation for the restroom exhaust fans (EF-1, 2, 3, 5, 7, 8, 9, 10, 12, 14) so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.]
2. Comment not addressed. [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope (e.g. the new glazing) based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.]
3. Comment not addressed. [Initial comment: Show that the proposed HVAC system meets the requirements of Sections C403.2, C403.3, IECC 2012 (e.g. provide the mechanical code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.]
06/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the Tucson Outdoor Lighting Code utilizing the 'SB' luminaires. Plan luminaire schedule shows them as uplights in a non totally enclosed arched roof.
06/08/2016 ROBERT SHERRY WATER REVIEW Completed
06/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A101; PREVIOUS COMMENT 11: IN THE PARTITION SCHEDULE, PLEASE INDICATE A ONE HOUR FIRE PARTITION. IN ADDITION, INDICATE THE U.L. LISTING NUMBER FOR THAT PARTITION ASSEMBLY.
2. SHEET G002: UNDER THE BUILDING HEIGHTS AND AREAS, PLEASE INDICATE THE ALLOWABLE AREA INCREASE PER THE IBC SECTION 506 ON THE DRAWING. INDICATE 9000 SF (300%) + 9000 = 36,000 SF ALLOWABLE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Relocate the shut off valve and check valve on the cold water line to a point upstream of the hot water return connection. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.]
2. Comment not addressed. [Initial comment: Specify the type of backflow prevention device required for the two irrigation outlets. Reference: Sections 608.1 and 608.3, IPC 2012.]
3. Correct the size of the gas pipe along the 70' branch to 1-1/4". [Initial comment: Revise the size of the natural gas pipe serving AC-1 and AC-2 (1" pipe @250' is limited to 119 CFH) per Table 402.4 (2). Reference: Section 402.4, IFGC 2012.]