Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM02955
Parcel: 132130950

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM02955
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 21: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
2. PREVIOUS COMMENT 3: PLEASE VERIFY ON THE DRAWINGS EXIT WIDTHS PROVIDED.
3. SHEET T1.1; CODE INFORMATION: PLEASE INDICATE ON THE DRAWINGS HOW THE 1580 TOTAL OCCUPANT LOAD WAS DERIVED. A NOTE INDICATES "OCCUPANT LOAD FROM TI 1580". THIS IS THE TI REVIEW. SHOW THE AREA OF EACH OCCUPANCY TYPE AND THE RESULTING OCCUPANT LOAD FOR THAT AREA.
4. SHEET T1.1; PLUMBING FIXTURE CALCULATIONS: PLEASE FOLLOW THE IBC SECTION 2902.1.1 FOR FIXTURE CALCULATIONS FOR MULTIPLE OCCUPANCIES. SHOW ALL CALCULATIONS ON THE DRAWINGS.
5. SHEET T1.1; PLUMBING FIXTURE CALCULATIONS: FOR THE 52 EMPLOYEES, ONE MEN'S AND ONE WOMEN'S RESTROOM IS REQUIRED. THE PLAN ON SHEET A1.3 INDICATES ONLY ONE TOILET TOTAL FOR EMPLOYEES. PLEASE REVISE.
6. GENERAL STRUCTURAL: PLEASE PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS. DARKEN THE HAND CALCULATIONS SO THEY ARE LEGIBLE.
7. GENERAL: PLEASE DARKEN THE CLOUDS AND REVISION NUMBERS ON THE DRAWINGS SO THEY ARE LEGIBLE.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL PREVIOUS COMMENTS IN ADDITION TO RESPONSES TO NEW COMMENTS.
07/08/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the total demand that the water meter will serve. [Initial comment: Provide the size of the water meter serving this building and the total demand that the meter will serve. Reference: Section 107.2.1, IBC 2012.]
07/11/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Third-party listing and material standards for the concrete lavatories have not been provided by the architect. [Initial comment: Provide third-party listing and material standards for all custom plumbing fixtures (e.g. LV-1). Reference: Sections 303.4, 402, and 416.1, IPC 2012.]
2. The fixture call-outs on sheets P1.1 and P2.1 still show the installation of LV-1 in the family restroom. [Initial comment: Coordinate the specified lavatory for the family restroom with the architect; the schedule on sheet A8.1 appears to call for a LV-2, not a LV-1. Provide tempered water for the lavatory in the family restroom using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012 and Section 107.2.1, IBC 2012.]
3. Show the required settings for the automatic faucets on the drawings so that the contractor will know how they are to be programmed. [Initial comment: Verify that the automatic faucets for the restroom lavatories will dispense a maximum of 0.25 gallons per metering cycle and that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]
4. Each individual appliance shall be provided with a backflow preventer. Note that the kitchen schedule shows a water connection to the grease recovery system; verify. [Initial comment: Individual appliances (e.g. blenders, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.]
5. Tea makers and coffee makers require the installation of a backflow prevention device that is listed to ASSE 1022. [Initial comment: Water supply connections to beverage dispensers shall, at a minimum, be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.]
07/13/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson has not adopted ASHRAE 62.1; ventilation calculations for multiple-zone HVAC units shall be per Section 403.3.2.3, IMC 2012. For all areas, the occupant loads shall be per Section 403.3, IMC 2012 unless approved statistical data is provided to document an alternate occupancy. [Initial comment: Provide calculations demonstrating adequate ventilation for the building. Reference: Section 403.2, IMC 2012.]
2. The requested structural calculations and details were not found in this submittal. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.]
3. The COMcheck Mechanical Compliance Certificate indicates that all of the roof top units are equipped with air economizers but this is not shown on the roof top unit schedule. Which is correct? Reference: Section C403.3.1, IECC 2012.
4. A revised submittal for three 4-ton split-system heat pump units was included with this submittal - wrong project?
07/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Still could not locate IECC code compliance or a written response for the lighting. Last plan review comment.
#2. Plan sheet E2.1 not in plan set as shown on title sheet drawing index.
Ref: 2012 IECC, 2012 IBC sec 107.2.1