Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2016 KEN BROUILLETTE FIRE REVIEW Approved
05/16/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this building and the total demand that the meter will serve. Reference: Section 107.2.1, IBC 2012.
05/17/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide third-party listing and material standards for all custom plumbing fixtures (e.g. LV-1). Reference: Sections 303.4, 402, and 416.1, IPC 2012.
2. Provide plumbing fixture calculations for the building. Reference: Section 403.1.1, IPC 2012.
3. Coordinate the specified lavatory for the family restroom with the architect; the schedule on sheet A8.1 appears to call for a LV-2, not a LV-1. Provide tempered water for the lavatory in the family restroom using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012 and Section 107.2.1, IBC 2012.
4. Verify that the automatic faucets for the restroom lavatories will dispense a maximum of 0.25 gallons per metering cycle and that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
5. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012.
6. Individual appliances (e.g. blenders, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
7. Water supply connections to beverage dispensers shall, at a minimum, be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
8. Verify that the discharge from the dishwasher (kitchen equipment number DW4) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.
9. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
05/17/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Provide calculations demonstrating adequate ventilation for the building. Reference: Section 403.2, IMC 2012.
3. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
4. Provide construction documents prepared by an Arizona registrant that demonstrate that the Type I and Type II exhaust systems comply with the requirements of Sections 506, 507 and 508, IMC 2012. Shop drawings are not an acceptable alternative.
05/20/2016 STEVE SHIELDS ZONING REVIEW Approved
05/20/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the 2012 IECC for interior lighting. Ref: 2012 IECC
05/20/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.1; BUILDING CODES: PLEASE REMOVE THE REFERENCE TO THE 2010 ADAAG ACCESSIBILITY CODE.
2. SHEET T1.1; EXIT CAPACITY: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
3. SHEET T1.1; EXIT CAPACITY: PLEASE VERIFY THE EXIT WIDTH PROVIDED (378"). THE EXIT DOORS AND WIDTHS PER SHEET A9.2 ARE E001(2-36" DOORS), E005 (48" DOOR), E006 (2-48" DOORS), E007 (36" DOOR), AND E008 (36" DOOR).
4. SHEET T1.1: PLEASE PROVIDE THE PLUMBING FIXTURE CALCULATIONS ON THE DRAWINGS, INCLUDING THE REQUIRED NUMBER OF MEN'S AND WOMEN'S WATERCLOSETS AND LAVATORIES, AND THE REQUIRED NUMBER OF SERVICE SINKS. INCLUDE IN THE ANALYSIS THE NUMBER OF PROVIDED FIXTURES FOR EACH ITEM.
5. SHEET A0.2 (EGRESS PLAN); SHEET A9.2 (DOOR SCHEDULE): AT EXIT E001, THE SCHEDULE INDICATES A PAIR OF 3'-0" X 8'-0" DOORS, WHILE THE EGRESS PLAN INDICATES 16'-0" EXIT DOORS (178" EGRESS WIDTH). PLEASE CLARIFY.
6. SHEET A1.2 (FLOOR PLAN); LEGEND: THIS PLAN DOES NOT APPEAR TO INCLUDE INTERIOR WALL TAGS. COULD THE LEGEND BE REMOVED FROM THIS SHEET? PLEASE VERIFY.
7. SHEET A1.2; FLOOR PLAN: THE POWER UP ENLARGED PLAN IS REFERENCED AS 08/A11.09. PLEASE REVISE THE REFERENCE NUMBER.
8. SHEET A3.1; KEYED NOTES: NOTE 13 REFERENCES DETAIL 8/A3.2. PLEASE REVISE THE REFERENCE NUMBER.
9. SHEET A3.2; DETAIL 12: A NOTE ON THIS DETAIL INDICATES TO 'REFER TO S-SHEETS FOR BRACING DETAIL'. PLEASE INDICATE A SPECIFIC DETAIL (POSSIBLY ON A11.2 OR S4.1).
10. SHEET A8.1 (ENLARGED TOILET PLAN 02); SHEET A8.2 (ELEVATIONS 12 AND 14): PLEASE REVERSE THESE ELEVATION NUMBERS TO MATCH THE PLAN.
11. SHEET A8.1; ENLARGED TOILET PLAN 01: INDICATE ON THE PLAN THE 30" X 48" CLEAR FLOOR SPACE REQUIRED AT THE ACCESSIBLE URINAL PER THE ICC/ANSI FIGURE 305.3.
12. SHEET A11.4; DETAIL 01: A NOTE ON THIS DETAIL INDICATES TO 'REFER TO S-SHEETS' FOR THE FOLDING PARTITION SUPPORT. PLEASE INDICATE A SPECIFIC REFERENCE (POSSIBLY ON S2.1).
13. SHEET A11.7; DETAIL 1: PLEASE PROVIDE ON THIS DETAIL THE STEEL PLATE SIZE AND THICKNESS AT THE TUBE COLUMN BASE. IN ADDITION, PROVIDE THE ANCHOR BOLT SIZE AND LENGTH.
14. SHEET A11.9; ENLARGED PLAN 03: A SECTION CUT ON THIS PLAN INDICATES 07/A11.9. PLEASE REVISE THE SECTION NUMBER.
15. SHEET A11.12; DETAIL 02: A NOTE ON THIS DETAIL INDICATES TO REFERENCE DETAIL 8/A11.1 FOR A STUD BOX HEADER SCHEDULE. PLEASE REVISE THAT DETAIL NUMBER.
16. SHEET A11.14: MUCH OF THE VERBIAGE ON THIS SHEET IS VERY LIGHT. PLEASE DARKEN.
17. SHEET A12.2: PLEASE INDICATE ON THIS SHEET THE NUMBER OF REQUIRED ACCESSIBLE DINING SURFACES PER THE IBC SECTION 1108.2.9.1, AND THE NUMBER PROVIDED.
18. SHEET S0.1; GENERAL NOTES (FOUNDATIONS): PLEASE PROVIDE ONE COPY OF THE GEOTECHNICAL REPORT FOR REVIEW.
19. SHEETS S1.1 AND S2.1: PLEASE DARKEN THE VERBIAGE AND KEYED NOTES.
20. GENERAL (STRUCTURAL): PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE FOLDING PARTITION SUPPORTS, BRACING, AND FOUNDATIONS.
21. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/20/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/26/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved