06/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT2; SHEET A1.1; SITE: REGARDLESS OF HOW FAR EXISTING STRUCTURES ARE FROM THE NEW COVERED PARKING CANOPIES, AND REGARDLESS OF THE STEEL CONSTRUCTION OF THE NEW CANOPIES, THE IBC AND A CODE INTERPRETATION FROM THE BUILDING OFFICIAL IN 2014 REQUIRE THE VERTICAL STRUCTURAL SUPPORT (TO THE FACE OF THE SUPPORT MEMBER) TO BE LOCATED A MINIMUM OF 5'-0" FROM THE PROPERTY/BUILDING LINE. IN ADDITION, THE ROOF PROJECTION OF THE NEW PARKING CANOPIES MUST BE LOCATED A MINIMUM OF 2'-0' FROM THE PROPERTY/BUILDING LINE. YOU MUST INDICATE ON THE DRAWINGS THAT THESE REQUIREMENTS ARE MET (SHOW ON A PLAN AND ADD A NOTE).
2. PREVIOUS COMMENT 7; SHEET S2.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (PURLIN DESIGN): THERE ARE STILL TWO INTERIOR SPANS (ON THE FRAMING PLAN AND ON THE FOUNDATION PLAN) THAT INDICATE AN 18'-0" MINIMUM SPAN. PLEASE REVISE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.