Permit Number: T16CM02954
Parcel: 140420600

Address:
6840 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM02954
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2016 DAVID RIVERA ZONING REVIEW Approved
06/01/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; SHEET INDEX: THE INDEX INDICATES SHEETS D1.0 AND D2.0. THESE ARE NOT IN THIS SUBMITTAL SET. PLEASE VERIFY.
2. SHEET A1.1; SITE PLAN: THE SETBACKS (FIRE SEPARATION DISTANCES) FOR THE NEW SHADE STRUCTURES ARE NOT INDICATED ON THE DRAWINGS. NO FIRE RESISTIVE RATING IS REQUIRED FOR THE STRUCTURES AS LONG AS THE VERTICAL STRUCTURAL SUPPORT IS A MINIMUM OF 5'-0" (TO THE FACE OF THE SUPPORT) FROM THE PROPERTY/BUILDING LINE, AND AS LONG AS THE ROOF PROJECTION OF THE SHADE STRUCTURES IS A MINIMUM OF 2'-0" FROM THE PROPERTY/BUILDING LINE. PLEASE INDICATE ON THE DRAWINGS THESE REQUIREMENTS ARE MET.
3. SHEET S1.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (PURLIN DESIGN): THE CALCULATIONS INDICATE A 9' PURLIN CANTILEVER AT THE EDGE SPAN, WHILE THE PLAN INDICATES A 10'-5" MINIMUM DIMENSION. PLEASE CLARIFY AND VERIFY THE PURLIN DESIGN.
4. SHEET S1.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (PURLIN DESIGN): THE CALCULATIONS INDICATE AN 18' PURLIN LENGTH AT THE INTERIOR SPAN, WHILE THE PLAN INDICATES AN 18'-0" MINIMUM DIMENSION. PLEASE CLARIFY AND VERIFY THE PURLIN DESIGN IF A SPAN OVER 18' IS USED.
5. SHEET S1.1 (DETAIL 10); STRUCTURAL CALCULATIONS (PURLIN SECTION INPUTS): THE CALCULATIONS INDICATE THE PURLIN HAS A THICKNESS OF 0.064", WHILE THE DETAIL INDICATES A t=0.055". PLEASE CLARIFY.
6. SHEET S2.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (PURLIN DESIGN): THE CALCULATIONS INDICATE A 9' PURLIN CANTILEVER AT THE EDGE SPAN, WHILE THE PLAN INDICATES A 17'-0" MINIMUM DIMENSION. PLEASE CLARIFY.
7. SHEET S2.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (PURLIN DESIGN): THE CALCULATIONS INDICATE AN 18' PURLIN LENGTH AT THE INTERIOR SPAN, WHILE THE PLAN INDICATES AN 18'-0" MINIMUM DIMENSION. PLEASE CLARIFY AND VERIFY THE PURLIN DESIGN IF A SPAN OVER 18' IS USED.
8. GENERAL: PLEASE PROVIDE DETAILS OR NOTES ON THE DRAWINGS FOR THE CONNECTION OF THE PHOTOVOLTAIC SYSTEM TO THE EXISTING BUILDING ROOF STRUCTURE, AND THE ADEQUACY OF THE EXISTING BUILDING ROOF STRUCTURE TO WITHSTAND THE NEW PHOTOVOLTAIC LOADS.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/03/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Please provide a grounding detail for grounding and or bonding PV panels, Strutural Steel, at the pv array locations ( canopys ) including hardware and equipment utilized, listed and identified for such use.
Ref: 2011 NEC 690 part V, and 250.4. 2012 IBC sec. 107.2.1
06/03/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Per additional info from the solar contractor, the review result was changed to approved.