Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM02891
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. As per the last plan review comments 6/27/16. "#1. Provide full compliance with the Tucson / Pima County Outdoor Lighting Code. #2. Designate type and include in the luminaire schedule all exterior lighting shown on plan sheet E-201. #3. Provide designation type, and include spec's in the luminaire schedule, include in the Outdoor Lighting calc's, for the LED accent lighting on the roof. Ref: 2012 IBC sec. 107.2.1, 2011 NEC." The led lighting on the roof is new this submittal and was not included in the original shell submittal. Therefore, this information must be included on the submitted electrical plans as required in section 104 of the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE, for this submittal. |
| 07/29/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/29/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/29/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |