Permit Number: T16CM02839
Parcel: 14118620A

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T16CM02839
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2016 CLAYTON TREVILLYAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Reqs Change Mechanical Comments:

1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
2. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2012.

Plumbing Comments:

1. Verify that the Pima County Regional Wastewater Reclamation Department will allow the drain from the sanitizing compartment of the 3-compartment sink and floor sink P-7 to bypass the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
2. Show how the mop sink is to be connected to the grease waste system. Reference: Section 107.2.1, IBC 2012 and Section 1003.3, IPC 2012, as amended by the City of Tucson.
3. A hydromechanical grease interceptor is limited to installations having no more than 4 fixtures connected to the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
4. Show how the required flow control device is to be installed and how the vent is to be routed. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
5. The vent for the gravity grease interceptor appears to be connecting to an existing underground vent that is serving some other use; is this correct or is it a drafting artifact? Reference: Section 905.5, IPC 2012.
05/09/2016 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size of the water meter serving the suite and the total demand that the meter serves (i.e. does the water meter serve only this suite).
2. Verify the actual water pressure for the suite; this is a low water pressure area. Reference: Section 604.7, IPC 2012.
05/09/2016 STEVE SHIELDS ZONING REVIEW Approved
05/09/2016 LOREN MAKUS ENGINEERING REVIEW Approved
05/09/2016 CLAYTON TREVILLYAN 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed Mechanical Comments:

1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
2. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2012.

Plumbing Comments:

1. Verify that the Pima County Regional Wastewater Reclamation Department will allow the drain from the sanitizing compartment of the 3-compartment sink and floor sink P-7 to bypass the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
2. Show how the mop sink is to be connected to the grease waste system. Reference: Section 107.2.1, IBC 2012 and Section 1003.3, IPC 2012, as amended by the City of Tucson.
3. A hydromechanical grease interceptor is limited to installations having no more than 4 fixtures connected to the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
4. Show how the required flow control device is to be installed and how the vent is to be routed. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
5. The vent for the gravity grease interceptor appears to be connecting to an existing underground vent that is serving some other use; is this correct or is it a drafting artifact? Reference: Section 905.5, IPC 2012.
07/13/2016 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2016 CPIERCE1 OUT TO CUSTOMER Completed