Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM02787
Parcel: 137055330

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM02787
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/25/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide cups for the bottle filler, located at an accessible location. [Initial comment: Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. service sink and two drinking fountains).]
04/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/25/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The sequence of operation for the exhaust fans is not clear but seems to conflict with key note #6 on sheet E1.00. Coordinate with the electrical design. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the fan will operate even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.]