Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM02787
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/25/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/25/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide cups for the bottle filler, located at an accessible location. [Initial comment: Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. service sink and two drinking fountains).] |
04/25/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/25/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The sequence of operation for the exhaust fans is not clear but seems to conflict with key note #6 on sheet E1.00. Coordinate with the electrical design. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the fan will operate even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.] |