Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02787
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 04/18/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the fan will operate even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012. |
| 04/18/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/19/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Min. font size for lettering on the plans is 3/32". Per City of Tucson Commercial Plan Review Requirements. |
| 04/19/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/19/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A3.0; DETAIL 7: PLEASE PROVIDE THE SIZE OF THE DIAGONAL BRACING AND THE CONNECTION TO THE TOP OF THE PARTITION AND TO THE STRUCTURE ABOVE. EXTEND THE DETAIL TO SHOW THE STRUCTURE ABOVE AND HOW THE BRACING CONNECTS TO THAT STRUCTURE. 2. SHEET A1.0; CODE INFORMATION: THE OCCUPANT LOAD MUST FOLLOW THE IBC SECTION 1004.1.2 (USING TABLE 1004.1.2). AN APPEAL TO THE BUILDING OFFICIAL MUST BE SUBMITTED TO REVISE THE OCCUPANCY LOAD (PER THE EXCEPTION TO SECTION 1004.1.2). THE OCCUPANT LOAD IS 22, THEREFORE A DRINKING FOUNTAIN AND SERVICE SINK ARE REQUIRED. PLEASE VERIFY. 3. SHEET A1.0; CODE INFORMATION: THE ANALYSIS INDICATES ONE EXIT IS PROVIDED, WHILE THE PLAN INDICATES TWO EXITS. PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/19/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. service sink and two drinking fountains). 3. The term "private" for plumbing fixtures applies to fixtures that are located in a residence or apartment, non-public toilet rooms in hotels or motels, and are intended for the use of a family or an individual. Revise the Plumbing Fixture Connection Schedule using public fixture units. Reference: Section 202, IPC 2012. 4. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012. 5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer). Reference: Section 604.9, IPC 2012. 6. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 7. Provide tempered water for the new restroom lavatory using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 8. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012. 9. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section C404.4, IECC 2012. 10. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012. |
| 04/19/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/20/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |