Permit Number: T16CM02739
Parcel: 125010460

Address:
48 N TUCSON BL

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM02739
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
05/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-5 (CONTROL JOINT DETAIL 7); STRUCTURAL CALCULATIONS (SHEET 3): A WALL PLAN SIMILAR TO THAT SHOWN IN THE CALCULATIONS SHOULD BE INCLUDED ON THE DRAWINGS TO INDICATE THE MASONRY REINFORCING AROUND THE GATES. A MASONRY CONTROL JOINT SHOULD ASLO BE INDICATED ON THAT PLAN IN THE 28' WALL RUN.
2. SHEET A-5 (SITE WALL DETAIL 4); STRUCTURAL CALCULATIONS (PAGE 2 OF THE WALL DESIGN): PLEASE CLARIFY THE FOOTING DESIGN AS SHOWN IN THE CALCULATIONS (5.34' FOOTING WIDTH X 4" THICK WITH A KEY) AND AS SHOWN ON THE DRAWINGS (CONTINUOUS 1'-6" FOOTING WIDTH X 2'-0" THICK).
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/11/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2016 KROBLES1 OUT TO CUSTOMER Completed