Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM02739
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/22/2016 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | LETTER SENT TO RECORDS |
05/09/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-5 (CONTROL JOINT DETAIL 7); STRUCTURAL CALCULATIONS (SHEET 3): A WALL PLAN SIMILAR TO THAT SHOWN IN THE CALCULATIONS SHOULD BE INCLUDED ON THE DRAWINGS TO INDICATE THE MASONRY REINFORCING AROUND THE GATES. A MASONRY CONTROL JOINT SHOULD ASLO BE INDICATED ON THAT PLAN IN THE 28' WALL RUN. 2. SHEET A-5 (SITE WALL DETAIL 4); STRUCTURAL CALCULATIONS (PAGE 2 OF THE WALL DESIGN): PLEASE CLARIFY THE FOOTING DESIGN AS SHOWN IN THE CALCULATIONS (5.34' FOOTING WIDTH X 4" THICK WITH A KEY) AND AS SHOWN ON THE DRAWINGS (CONTINUOUS 1'-6" FOOTING WIDTH X 2'-0" THICK). 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
05/11/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/21/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |