Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM02653
Parcel: 12404032B

Address:
1443 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02653
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Watts model LF 007 is listed to ASSE 1015; the requirement is for a backflow device that is listed to ASSE 1022. [Second comment: See Section 608.16.10, IPC 2012 (the 2012 IPC is the code you stated that you used to design the plumbing system); it requires a backflow preventer conforming to ASSE 1022 for all beverage dispensers. The 2006 UPC is not in use at this time but Section 603.5.12, UPC 2012 also requires the use of a backflow preventer conforming to ASSE 1022.] [Initial comment: Provide an ASSE 1022-listed backflow prevention device for all beverage dispensers that are directly-connected to water.]