Permit Number: T16CM02653
Parcel: 12404032B

Address:
1443 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02653
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2016 ANDREW CONNOR ZONING REVIEW Approved
04/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new heat pump.
2. Provide exhaust for the relocated cooking appliances that do not require a Type II hood. Reference: Section 507.2.2, IMC 2012.
04/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/12/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PLEASE PROVIDE THE NEW STEEL COLUMN BASE PLATE SIZE AND ANCHOR BOLT SIZE AND LENGTH ON DETAIL 101 ON SHEET S2.
04/12/2016 ROBERT SHERRY WATER REVIEW Completed
04/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an ASSE 1022-listed backflow prevention device for all beverage dispensers that are directly-connected to water.
2. Verify with RWRD that the hand sink and floor sink will not be required to be connected to the grease waste system.
04/12/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/13/2016 MARTIN BROWN FIRE REVIEW Approved