Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02650
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/12/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
04/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
04/12/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a complete panel schedule and load calc for panel 7P. #2. Update the registrant stamp exp. date. Ref: IBC 107.2.1 |
04/12/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/12/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; WALL SECTION 2: PLEASE PROVIDE THE DIAGONAL BRACE SIZE, AND INDICATE THE NUMBER AND SIZE OF CONNECTORS TO THE PARTITION WALL AND TO THE STRUCTURE ABOVE. EXTEND THE SECTION TO SHOW THE CONNECTION TO THE STRUCTURE ABOVE. |
04/12/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
04/12/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/13/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |