Permit Number: T16CM02622
Parcel: 117101240

Address:
220 N MEYER AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02622
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
04/11/2016 KEN BROUILLETTE FIRE REVIEW Approved
04/20/2016 ANDREW CONNOR ZONING REVIEW Approved
04/20/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following plan review comments.
#1. Provide a complete panel schedule for panel 'A'.
#2. Load calc's for new 200 Amp service.
#3. Complete luminaire schedule for new interior lighting.
#4. Provide a disconnect switch for the new water heater.
#5. Kitchen 120V receptacles to GFI protected.
#6 Provide conduit types and sizes for the panel feeders.
Ref: 2012 IBC 107.2.1
04/21/2016 ARUIZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
04/21/2016 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
04/21/2016 ARUIZ1 WATER REVIEW Needs Review
04/21/2016 ARUIZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
04/21/2016 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review