Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02622
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
04/11/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
04/20/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
04/20/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following plan review comments. #1. Provide a complete panel schedule for panel 'A'. #2. Load calc's for new 200 Amp service. #3. Complete luminaire schedule for new interior lighting. #4. Provide a disconnect switch for the new water heater. #5. Kitchen 120V receptacles to GFI protected. #6 Provide conduit types and sizes for the panel feeders. Ref: 2012 IBC 107.2.1 |
04/21/2016 | ARUIZ1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
04/21/2016 | ARUIZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
04/21/2016 | ARUIZ1 | WATER | REVIEW | Needs Review | |
04/21/2016 | ARUIZ1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
04/21/2016 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |