Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM02618
Parcel: 133369580

Address:
70 N HARRISON RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02618
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2016 MARTIN BROWN FIRE REVIEW Approved
04/28/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET C.1; CODE REVIEW (PLUMBING REQUIREMENTS): THE REQUIRED LAVATORIES PER TABLE 2902.1 IS ONE PER SEX (1/40). PLEASE REVISE ON THIS SHEET.
2. SHEET C.1; EGRESS PLAN: THE ACTUAL NUMBER OF OCCUPANTS EXITING THROUGH THE SOUTH DOOR DOES NOT SHOW UP ON THE PLAN. PLEASE ADD.
3. SHEET C.1; CODE REVIEW (ALLOWABLE TRAVEL DISTANCE): PLEASE INDICATE ON THE DRAWING THE ALLOWABLE TRAVEL DISTANCE PER THE IBC TABLE 1016.2 IS 300'.
4. SHEET C.1; APPLICABLE CODES: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THE LIST.
5. SHEETS C.2 AND C.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
6. SHEET A.1; DEMOLITION KEYNOTES: NOTE 10 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
7. SHEET A.2; FLOOR PLAN KEYNOTES: NOTES 3, 6, AND 13 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
8. SHEET A.2; FLOOR PLAN: DETAIL 16/A.6 IS INDICATED IN SEVERAL LOCATIONS AT THE EXTERIOR WALL. PLEASE REVISE THE DETAIL NUMBER.
9. SHEET A.3; PLANS 1, 2, AND 5: DETAIL/SECTION CUTS ON THESE PLANS ALL INDICATE SHEET A.6. PLEASE REVISE THE DETAIL/SECTION NUMBER.
10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/02/2016 ROBERT SHERRY WATER REVIEW Completed
05/02/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. According to Tucson Water, the water pressure range at 70 N. Harrison Road is 31.1 to 38.1 PSI. Revise the water pressure calculations accordingly. Reference: Section 604.1, IPC 2012.
2. Correct the size of the horizontal drain located directly west of restroom A115: the size should be 3", not 4". Reference: Section 706.2, IPC 2012.
3. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
05/02/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide for wiring methods in the patient care and exam rooms to comply with NEC 517.13.
#2. Revise the one line diagram and the panel schedules so they correlate. ( labeling and ampacity ) Ref: 2012 IBC 107.2.1, 2011 NEC.