Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02618
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/28/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET C.1; CODE REVIEW (PLUMBING REQUIREMENTS): THE REQUIRED LAVATORIES PER TABLE 2902.1 IS ONE PER SEX (1/40). PLEASE REVISE ON THIS SHEET. 2. SHEET C.1; EGRESS PLAN: THE ACTUAL NUMBER OF OCCUPANTS EXITING THROUGH THE SOUTH DOOR DOES NOT SHOW UP ON THE PLAN. PLEASE ADD. 3. SHEET C.1; CODE REVIEW (ALLOWABLE TRAVEL DISTANCE): PLEASE INDICATE ON THE DRAWING THE ALLOWABLE TRAVEL DISTANCE PER THE IBC TABLE 1016.2 IS 300'. 4. SHEET C.1; APPLICABLE CODES: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THE LIST. 5. SHEETS C.2 AND C.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 6. SHEET A.1; DEMOLITION KEYNOTES: NOTE 10 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY. 7. SHEET A.2; FLOOR PLAN KEYNOTES: NOTES 3, 6, AND 13 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY. 8. SHEET A.2; FLOOR PLAN: DETAIL 16/A.6 IS INDICATED IN SEVERAL LOCATIONS AT THE EXTERIOR WALL. PLEASE REVISE THE DETAIL NUMBER. 9. SHEET A.3; PLANS 1, 2, AND 5: DETAIL/SECTION CUTS ON THESE PLANS ALL INDICATE SHEET A.6. PLEASE REVISE THE DETAIL/SECTION NUMBER. 10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/02/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/02/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. According to Tucson Water, the water pressure range at 70 N. Harrison Road is 31.1 to 38.1 PSI. Revise the water pressure calculations accordingly. Reference: Section 604.1, IPC 2012. 2. Correct the size of the horizontal drain located directly west of restroom A115: the size should be 3", not 4". Reference: Section 706.2, IPC 2012. 3. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
| 05/02/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/09/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide for wiring methods in the patient care and exam rooms to comply with NEC 517.13. #2. Revise the one line diagram and the panel schedules so they correlate. ( labeling and ampacity ) Ref: 2012 IBC 107.2.1, 2011 NEC. |