Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM02517
Parcel: 13707046D

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM02517
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/06/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the driver's restroom is equipped with mechanical ventilation per Table 403.3, IMC 2012.
2. Provide locking access port caps on the new condensing unit if the condensing unit is not within enclosed cage.Reference: Section 1101.10.
04/06/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide disconnecting means for the transformer as required per NEC art. 450.14
#2. Ref, plan sheet E1.0. Load calc's do not cooralate with loadcenter designations shown on the plans. ( Panel 'LA' ) ?
#3. Indicate all feeder and branch circuit conduit, conductor, sizes and types on the plans.
#4. Provide a complete power plan E1.1. Include the information building panel location and information booth location. Provide additional information for the note, "intercept UGE conduit" and the removal of existing conductors, and provide feeders for information booth ?
Ref: 2012 IBC sec. 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements
04/06/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the water pressure/pipe sizing calculations for this activity.
2. Correct the water fixture units for the new flush valve water closets
3. Verify that the existing water closets are indeed tank-type fixtures.