Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM02480
Parcel: 12109006A

Address:
5151 E PIMA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM02480
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/09/2016 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/09/2016 PIBARRA1 APPROVAL SHELF Completed
11/09/2016 PIBARRA1 OUT TO CUSTOMER Completed
11/09/2016 PIBARRA1 REJECT SHELF Completed