Permit Number: T16CM02469
Parcel: 10703140B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM02469
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please verify new ckt #29 on panel A. This circuit is designated to receptacles on the power plan.
2012 IBC 107.2.1, 2011 NEC
04/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT; SHEET A1.0; FLOOR PLAN: IT STILL APPEARS THERE MIGHT BE A PROBLEM WITH THE COMMON PATH OF EGRESS TRAVEL FROM STORAGE ROOM 117 TO THE MAIN EXIT EXCEEDING THE IBC TABLE 1014.3, SINCE YOU CAN'T GO THROUGH THE STORAGE ROOM 118. PLEASE INDICATE THIS PATH ON THE PLAN AND SHOW THE DISTANCE MEETS THE CODE REQUIREMENT.
2. PREVIOUS COMMENT; GENERAL: ON THE NEW DETAIL 5/A2.0 FOR THE WATER HEATER SUPPORT, PROVIDE THE ANGLE IRON FRAME SPACING. THE ANCHOR SIZE, QUANTITY, AND LENGTH AT THE WALL MUST BE SPECIFIED (CANNOT USE APPROVED MANNER).
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.