Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02469
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/14/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1.0; FLOOR PLAN: IN THE BREAK ROOM, PLEASE INDICATE THE COUNTER TOP/SINK IS LOCATED 34" ABOVE THE FINISH FLOOR. 2. SHEET A1.0; FLOOR PLAN: IT STILL APPEARS THERE MIGHT BE A PROBLEM WITH THE COMMON PATH OF EGRESS TRAVEL FROM STORAGE ROOM 117 TO THE MAIN EXIT EXCEEDING THE IBC TABLE 1014.3, SINCE YOU CAN'T GO THROUGH THE STORAGE ROOM 118. PLEASE INDICATE THIS PATH ON THE PLAN AND SHOW THE DISTANCE MEETS THE CODE REQUIREMENT. 3. GENERAL: ON SHEET P2.0, A NEW WATER HEATER IS INDICATED AND A DETAIL 2 IS SHOWN INDICATING THE WATER HEATER IS MOUNTED ABOVE THE RESTROOM CEILING. PLEASE INDICATE THE NEW WATER HEATER ON SHEET A1.0, AND PROVIDE A DETAIL FOR THE WATER HEATER SUPPORT. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/18/2016 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |