Permit Number: T16CM02469
Parcel: 10703140B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02469
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/05/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the Packaged Heating/Cooling Unit Schedule and coordinate with the mechanical plans.
2. Identify the reason for EF-2.
04/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2016 ROBERT SHERRY WATER REVIEW Completed
04/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: ALTHOUGH THERE ARE ONLY 49 OCCUPANTS, THE COMMON PATH OF EGRESS TRAVEL PER THE IBC TABLE 1014.3 APPEARS TO BE EXCEEDED, THEREFORE AT LEAST TWO EXITS ARE REQUIRED. PLEASE INDICATE ON THE PLAN THE MEANS OF EGRESS FOR THE 49 OCCUPANTS.
2. GENERAL: IT IS NOT CLEAR ON THE PLAN HOW THE RESTROOMS ARE ACCESSED WITHOUT GOING THROUGH LAB ROOMS OR KITCHENS. PLEASE INDICATE.
3. GENERAL: PLEASE INDICATE ON THE PLAN THE MEN'S, WOMEN'S, AND UNISEX RESTROOMS.
4. GENERAL: A FULL REVIEW OF THIS PROJECT HAS NOT BE MADE. WHEN THE ABOVE ISSUES HAVE BEEN CLARIFIED, A FULL REVIEW WILL BE COMPLETED.
5. GENERAL: THIS FLOOR PLAN WILL NOT WORK IF NEW TENANTS ARE IN THE LEASE SPACES. PLEASE ADDRESS.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/06/2016 MARTIN BROWN FIRE REVIEW Approved
04/14/2016 ARUIZ1 ZONING REVIEW Needs Review