Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/18/2016 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
04/22/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Footnote b on Table 403.3 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. Reference: Section 403.2.1 (3), IMC 2012. 2. Revise the ventilation calculations to include the exhaust required for kitchens. Reference: Sections 403.3 and 507.2.2, IMC 2012. |
04/22/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. 2. Verify that the Pima County Regional Wastewater Reclamation Department will allow the indirect drain from the espresso machine to bypass the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. |