Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM02457
Parcel: 12405007B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM02457
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2016 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
04/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Footnote b on Table 403.3 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. Reference: Section 403.2.1 (3), IMC 2012.
2. Revise the ventilation calculations to include the exhaust required for kitchens. Reference: Sections 403.3 and 507.2.2, IMC 2012.
04/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
2. Verify that the Pima County Regional Wastewater Reclamation Department will allow the indirect drain from the espresso machine to bypass the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.