Permit Number: T16CM02457
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02457
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2016 STEVE SHIELDS ZONING REVIEW Approved
04/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
04/04/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/04/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2; FLOOR PLAN 1: PLEASE REVISE THE ELEVATION REFERENCE OF 7/A5.
2. SHEET A3; ABOVE COUNTER PLAN 1: PLEASE INDICATE ELEVATION B/A5 ON THE PLAN.
3. SHEET A5; DETAIL 1: PLEASE INDICATE THE SIZE AND QUANTITY OF CONNECTORS FOR THE KICKERS (AT TOP OF PARTITION AND TO STRUCTURE ABOVE).
4. GENERAL: THIS RETAIL OCCUPANCY TYPE (M) DOES NOT FIT THIS TYPE OF OCCUPANCY WHERE AN OVEN FOR BAKING IS LOCATED. THIS CHANGE COULD AFFECT THE OCCUPANCY LOAD AND PLUMBING REQUIREMENTS. PLEASE VERIFY THE OCCUPANCY CLASSIFICATION USING THE IBC CHAPTER 3.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/04/2016 ROBERT SHERRY WATER REVIEW Completed
04/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/05/2016 MARTIN BROWN FIRE REVIEW Approved