Permit Number: T16CM02449
Parcel: 140292040

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02449
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/09/2016 ROBERT SHERRY WATER REVIEW Completed
09/09/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide disconnecting means and overcurrent protection for the secondary tap conductors of transformer TCR as required per NEC art. 240.21 and 450.21.
09/09/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Computer rooms require ventilation; show how this is to be accomplished. Reference: Section 403.3, IMC 2012.
09/19/2016 KROBLES1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2016 KROBLES1 OUT TO CUSTOMER Completed