Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02449
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/09/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/09/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/09/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide disconnecting means and overcurrent protection for the secondary tap conductors of transformer TCR as required per NEC art. 240.21 and 450.21. |
| 09/09/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Computer rooms require ventilation; show how this is to be accomplished. Reference: Section 403.3, IMC 2012. |
| 09/19/2016 | KROBLES1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |