Permit Number: T16CM02436
Parcel: 133180220

Address:
7041 E 2ND ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T16CM02436
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM02436
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". See electrical comments.
2. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. One story dwellings must have a gray drain line discharge. Additional gray fixture drains are optional. Show a second clothes washer standpipe plumbed to an exterior wall above grade, or a bathing fixture drain looped 3' beyond an exterior wall below grade before connection to the building drain. See details at http://pdsd.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf

SITE PLAN:

1. Indicate the location of gas lines from property line to building, R106.1.1.

FLOOR PLANS:

1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1. Update the front porch elevation marker on sheet #2.
2. Show the location of a minimum 22" x 30" attic access. Attic access is required for areas exceeding 30 SQ FT with a minimum of 30" of headroom and located in a hallway or readily accessible space, R807.1, or show passage between the proposed and existing accessible attic areas.

ELEVATIONS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806.
2. If a vented roof assembly method will be utilized then provide an attic space ventilation calculation and specify size and location of all vents needed to comply with R806.2. Show a roof ventilation plan with a minimum 1" air space between the insulation and roof sheathing. Provide appropriate upper and lower space vents if applying the reduced area calculation per exception requirements.

PLUMBING PLANS:

1. A single story dwelling with the clothes washer at an interior wall requires only one gray water fixture preparation with under floor gray drainage plumbing, Ordinance #11089. Provide a bathing fixture drain looped 3' beyond an exterior wall below grade before connection to the building drain. See details at http://pdsd.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal. The deferred calculations must be approved through revision process prior to mechanical inspections.

ELECTRICAL PLANS:

1. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.
2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2016 ARUIZ1 OUT TO CUSTOMER Completed