Permit Number: T16CM02393
Parcel: 116162510

Address:
1001 N MAIN AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM02393
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2016 MARTIN BROWN FIRE REVIEW Approved
04/20/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1; CODE CHECK (GENERAL BUILDING HEIGHT): NOTE 3 INDICATES TYPE IV CONSTRUCTION. PLEASE REVISE.
2. SHEET G1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE AS REQUIRED.
3. SHEET A1; REFLECTED CEILING PLAN: A SECTION CUT REFERENCES 6/A4. PLEASE REVISE THE REFERENCE.
4. SHEET A2; SECTION 2: AN ENLARGED WALL DETAIL REFERENCES 4/A3. PLEASE REVISE THE REFERENCE.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified urinal meets the hydraulic performance requirements of ASME A112.19.2/CSA. Reference: Section 419.1, IPC 2012.
2. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
3. Clarify the lack of tempered water for the restroom lavatories. Reference: Sections 416.5 and 607.1.2, IPC 2012.
4. The rim elevation of the next upstream sanitary manhole (#6646-02, 2355.1') is less than 12" below the first floor elevation (2355.8'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
04/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/22/2016 ROBERT SHERRY WATER REVIEW Completed
04/25/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Estevan Park Comfort Station
T16CM02393
Building Plan (1st Review)

TRANSMITTAL DATE: April 25, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As a new structure is proposed on site a development package is required to be reviewed and approved prior to approval of the building plans. As this is a minor change to the park site Zoning is willing to do the development package review as an over-the-counter review on an hourly basis.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/02/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a complete grounding electrode system as required per 2011 NEC arts. 250.32 and 250.50 at the new structure.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2016 KROBLES1 OUT TO CUSTOMER Completed