Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM02286
Parcel: 11307003A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02286
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2016 MARTIN BROWN FIRE REVIEW Approved
04/14/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.0 (CODE REVIEW); SHEET C1.0 (SITE PLAN): THE SITE PLAN INDICATES TENANT IMPROVEMENT #2837 HAS 1000 SF. THE CODE REVIEW INDICATES A BUILDING AREA OF 2875 SF AND 22 OCCUPANTS. SHEET C1.0 INDICATES #2839 TO THE WEST OF THIS TENANT IMPROVEMENT AS 1900 SF. ARE WE COMBINING TWO SEPARATE ADDRESSES TO CREATE A SINGLE TENANT SPACE? PLEASE CLARIFY.
2. SHEET D1.0; DEMOLITION REFLECTED CEILING PLAN: KEYNOTE 7 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
3. SHEET D1.0; DEMOLITION FLOOR PLAN: KEYNOTE 15 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
4. SHEET A1.0; FLOOR PLAN: PER THE IBC SECTION 1004.1.2, AREAS WITHOUT FIXED SEATING MUST DETERMINE THE OCCUPANT LOAD USING TABLE 1004.1.2. THE ACTUAL NUMBER OF OCCUPANTS MAY BE REDUCED BY AN APPEAL TO THE BUILDING OFFICIAL PER SECTION 1004.1.2(EXCEPTIONS). PLEASE VERIFY.
5. SHEET A1.0; FLOOR PLAN: PER THE IBC TABLE 1015.1 AND THE OCCUPANT LOAD LISTED, ONLY ONE EXIT IS REQUIRED. IF THE ACTUAL COMMON PATH OF EGRESS TRAVEL EXCEEDS THE VALUE IN THE IBC TABLE 1014.3, ANOTHER EXIT IS REQUIRED. THE EXITS ON THE NORTH WALL OF STORAGE ROOMS 9 AND 10 DO NOT MEET THE REQUIREMENTS OF SECTION 1014.2(4). PLEASE REVIEW THESE ISSUES.
6. SHEET A1.0; FLOOR PLAN: PER THE IBC SECTION 1014.2, EGRESS TO A REQUIRED FACILITY SHALL NOT PASS THROUGH KITCHENS. TO ACCESS RESTROOM 17, THE ROUTE PASSES BETWEEN THE THREE COMPARTMENT SINK AND THE ROASTER ROOM. PLEASE CLARIFY.
7. SHEET A1.0; FLOOR PLAN: PER THE IBC SECTION 2902.2, SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. PLEASE REVISE THE UNI-SEX RESTROOMS INTO ONE MEN'S AND ONE WOMEN'S.
8. SHEET A1.0; PLUMBING FIXTURE CALCULATION: THE IBC SECTION 303.1.1 ALLOWS ASSEMBLY USES WITH AN OCCUPANT LOAD OF LESS THAT 50 TO BE CLASSIFIED AS A B OCCUPANCY. HOWEVER, THE OCCUPANT LOAD MUST BE CALCULATED AS AN A-2, AND THEN MAY BE CLASSIFIED AS A B IF THE REQUIREMENTS OF SECTION 303.1.1 ARE SATISFIED.
9. SHEET A3.0; DETAIL 4: THE BARN DOOR MAY NOT HAVE A LOCKSET AS PART OF THE HARDWARE, OR IF IT IS LOCKABLE, A SIGN PER THE IBC SECTION 1008.1.9.3 MUST BE INDICATED. PLEASE INCLUDE THIS ON THE DRAWINGS.
10. SHEET A4.0 (DETAIL 5); SHEET A4.1 (ELEVATION 2): PER THE ICC/ANSI SECTION 902, THE HEIGHT OF THE COFFEE BAR COUNTERTOP AND SINK MUST BE A MAXIMUM OF 34" ABOVE FINISH FLOOR. PLEASE VERIFY FOR ALL COFFEE BAR ELEVATIONS ON THIS SHEET.
11. SHEET A4.1; ELEVATIONS 7 AND 8: ARE THESE REVERSED ON THE ENLARGED PLAN 1? PLEASE VERIFY.
12. SHEET A4.2; KEYNOTES: NOTE 18 INDICATES A WATER HEATER PLATFORM BY G.C. INCLUDE ON THESE DRAWINGS DETAILS, NOTES, AND PLANS AS REQUIRED TO INDICATE THE PLATFORM CONSTRUCTION AND ALL PERTINENT DETAILS INCLUDING MEMBER SIZES, CONNECTIONS, WALL BRACING, ETC. IT IS THE RESPONSIBILITY OF THE LICENSED ARCHITECT IN RESPONSIBLE CHARGE TO PROVIDE THIS INFORMATION.
13. GENERAL: AT THE WALL KEYNOTES 1 AND 12 ON SHEET A1.0, PLEASE INDICATE THE WALL HEIGHT (TO ROOF DECK OR JUST ABOVE THE CEILING). IF THE PARTITION STOPS JUST ABOVE THE CEILING, INDICATE DIAGONAL BRACING SIZE AND SPACING, AND CONNECTORS (SIZE AND QUANTITY) FOR THE BRACING TO THE TOP OF THE PARTITION AND TO THE ROOF STRUCTURE ABOVE. INCLUDE DETAILS AS REQUIRED.
14. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/15/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide a reduced pressure backflow prevention assembly to be installed directly after the water meter for the water service to the building. Show the location of the assembly on the drawings. Reference: Section 107.2.1, IBC and Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
04/15/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the waste and vent schematic with the plumbing plans. Reference: Section 107.2.1, IBC 2012.
2. The size of the fixture drain serving the clothes washer and lavatory L-2 is not specified. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012.
3. Tucson Water estimates that the water pressure range for this address will be 41 to 48 PSI, not the 60 PSI value used to determine the pipe sizes. Reevaluate the pipe sizes based on the expected minimum water pressure. Reference: Section 604.1 and E201.1 (2), IPC 2012.
4. Clarify the purpose of installing a backflow preventer (General Note 9 on sheet P1.1, Watts 9DM) on equipment with solenoid valves but not installing water hammer arrestors (ASSE 1010). Reference: Section 604.9, IPC 2012.
5. Detail 1/P2.1 shows a recirculating hot water system. If this is intended, show the size and routing of the hot water return piping on the plumbing plan. Reference: Section 607.2, IPC 2012.
6. Specify the type of backflow prevention device required for each direct water connection to an appliance. Reference: Sections 608.1 and 608.3, IPC 2012.
7. Water supply connections to beverage dispensers (e.g. coffee makers, etc.) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
8. The Kitchen Equipment Schedule on sheet A4.1 calls for a 0.5" direct drain connection for the side rinse spray (K-1); show how this is to be accomplished. Reference: Section 702.1, IPC 2012.
9. Provide a direct connection for the bar sink (K-13). Reference: Sections 301.3 and 802.1, IPC 2012.
10. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
11. Correct General Note 22 on sheet P1.1 to comply with the requirements of the 2012 IPC. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012.
12. Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2012, as amended by the City of Tucson.
13. Correct the total natural gas load shown in the gas schematic on sheet P3.1; the total load is 260 MBH, not 225 MBH. Based on a total developed pipe length of 149 feet, the natural gas pipe serving the coffee roaster is undersized per Table 402.4 (2). Reference: Section 402.4, IFGC 2012.
14. Revise detail 1/P2.1 to show the location of the sediment trap downstream of the appliance shut off valve. Reference: Section 408.4, IFGC 2012.
15. Detail 1/M1.1 shows the direct venting configuration for the water heater using 2" CPVC. Provide the maximum developed vent length information for the 2" CPVC instead of the information for 3" CPVC. Verify that the termination of the vent complies with the manufacturer's installation instructions for clearances. Reference: Section 503.8, IFGC 2012.
04/18/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide exhaust for the new restroom (formerly an office). Verify that the existing (but modified) restroom also has sufficient exhaust flow. Reference: Section 403.3, IMC 2012.
2. Provide balancing information for the existing HVAC system so that the balancing contractor can verify that the calculated quantities of outside air are being delivered to the various occupancy zones. Reference: Sections 403.3 and 403.7, IMC 2012.
3. Revise the ventilation calculations to determine the minimum required outside air for a recirculating system serving multiple zones. Reference: Section 403.3.2.3, IMC 2012.
4. An exhaust duct for a domestic dryer is required to be 4" in diameter. Reference: Sections 304.1 and 504.6.1, IMC 2012.
5. Clarify how the existing furnace and packaged rooftop unit work together with respect to outside air delivery. Reference: Sect6ion 107.2.1, IBC 2012.
04/18/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principal Planner

PROJECT: 2837 N. Campbell Avenue
T16CM02286
Building Plan (1st Review)

TRANSMITTAL DATE: April 19, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Sheet C1.0 as it appears that you are proposing site changes a development package review is required.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/26/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.#1. Minimum lettering font size is 3/32" ( plan sheet E0.2 ) per City of Tucson Commercial Plan Submittal Requirements. #2. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.