Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW - RESIDENTIAL
Permit Number - T16CM02279
Review Name: 3RD PARTY REVIEW - RESIDENTIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Steve Shields, Principal Planner PROJECT: T15CM02279 573 S. 9th Avenue New Single Family Residence TRANSMITTAL: May 18, 2016 COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HC-3 zone (UDC 4.7.22). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-4). The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). Based on a proposed wall height of 17'-3" the required front street perimeter yard setback is 25'-11", proposed front street perimeter yard setback is 0'-0". The historic review will need to be completed and approved prior to approval of the building plans. If the historic review is approved provide the historic case number in the lower right hand corner of the plot plan and if applicable provide a general note that provides the historic case number date of approval, and any conditions of approval . |
| 05/31/2016 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Approved |