Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM02245
Parcel: 10820051H

Address:
4036 N 1ST AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM02245
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide load calcs on the panel schedule for Panel L.
Ref: 2012 IBC 107.2.1 ,2011 NEC 408.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2017 LBOJORQ1 OUT TO CUSTOMER Completed