Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2016 STEVE SHIELDS ZONING REVIEW Approved
03/25/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/25/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/25/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide accessible controls for the shower compartment. Reference: Section 404, IPC 2012.
2. Provide a water pressure regulator for the water service to the building. Reference: Section 604.8, IPC 2012.
3. Clarify the location of water heater WH-1 and show how the T&P relief pipe is able to reach to mop sink. Verify that the mop sink is a floor-level unit.
03/25/2016 ROBERT SHERRY WATER REVIEW Completed
03/25/2016 MARTIN BROWN FIRE REVIEW Approved
03/30/2016 RBENT1 BUILDING-COMMERCIAL REVIEW Completed
03/30/2016 RBENT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed