Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM02221
Parcel: 12417198C

Address:
1095 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02221
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2016 ANDREW CONNOR ZONING REVIEW Approved
03/25/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/25/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/25/2016 ZENEWCOM BUILDING-COMMERCIAL REVIEW Approved
03/25/2016 ROBERT SHERRY WATER REVIEW Reqs Change 1. Verify the existance of a 5/8" water meter at the address - Tucon water shows a 1" water service at that address but no existing water meter.
2. Show the location of the backflow preventer.
03/25/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Complete the water calculation on sheet 2: PSID/100-feet?
2. Verify the size of the building sewer - it is shown as both 3" and 4".
3. An approved 2-way cleanout maybe installed where the building sewer and the building drain connect but at no other location.
4. Provide the rim elevation and invert for both the upstream and downstream manholes along with the first floor elevation of the building.
5. Provide a full-way shutoff valve for the water service at the building entrance.
6. Provide a current model number for the lavatory faucet. Verify that the unit will deliver a maximumn of 0.25 Gallons per cycle and operate for at least 10-seconds for accessibility.
03/25/2016 MARTIN BROWN FIRE REVIEW Approved
03/25/2016 ZENEWCOM COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2016 RBENT1 APPROVAL SHELF Completed
03/29/2016 RBENT1 OUT TO CUSTOMER Completed
03/29/2016 RBENT1 REJECT SHELF Completed