Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T16CM02179
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Steve Shields, Lead Planner PROJECT: T16CM02179 3229 E. Bellevue Street Attached Carport TRANSMITTAL: March 23, 2016 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height less than 9'-0" the required perimeter yard setback to the west property line is 6'-0" proposed setback is 1'-0". |
| 03/23/2016 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 04/27/2016 | ARUIZ1 | ENGINEERING | REVIEW | Needs Review | |
| 04/27/2016 | ARUIZ1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |