Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM02158
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/29/2016 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1. THE BUILDING DATA STATES THE SF IS 2750, BUT THE SQUARE FOOTAGE USED TO DETERMINE OCCUPANT LOAD IS 2168. PLEASE CLARIFY 2. PLEASE INDICATE THE SIZE AND LOCATION OF CARBON DIOXIDE SYSTEMS FOR BEVERAGE MACHINES. 3. THE SEATING PLAN INDICATES 70 SEATS. THE OCCUPANT LOAD DATA INDICATES 48. IF YOU ADD THE PROPOSED 70 SEATS TO THE CALCULATED QUEING AND WAITING AREA THE OCCUPANT LOAD EXCEEDS 100 AND AN AUTOMATIC FIRE SPRINKLER SYSTEM IS REQUIRED. |
| 04/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Appliances (e.g. ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 2. Water supply connections to beverage dispensers (e.g. K-2 and K-8) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. 3. Revise the natural gas piping information to show the developed lengths of the piping from the meter to each load. Coordinate the loads shown on the plan with the load totals shown in the note next to the gas meter (i.e. missing 144 MBH?). Reference: Section 107.2.1, IBC 2012. 4. Verify that the required minimum gas pressure for the new fryer can be accommodated by the low pressure gas service. Reference: Section 402.1, IFGC 2012. |
| 04/12/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012. (Note: Replacement of up to 25% of the existing building fenestration will require that the U-factor and SHGF of the replacement fenestration be equal to or lower than the existing fenestration. Replacement of more than 25% of the fenestration will require the new fenestration to comply with the U-factor and SHGF values of the 2012 IECC. Reference: Section 5.1.3, exception g, ASHRAE Standard 90.1-2010 and C402.3.3, IECC 2012.) 2. Provide non-combustible insulation for the makeup air duct within 18" of the Type I hood. Reference: Section 506.3.1.2, IMC 2012. 3. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. 4. Show that the hood installation complies with Section 507.9, IMC 2012 for clearances at the back, sides and top of the hood (i.e. clarify the construction of the surrounding walls and the clearance from combustible materials above the hood). 5. Verify the amount of carbon dioxide stored within the building. If the carbon dioxide storage consists of more than two 50-pound cylinders, provide a mechanical exhaust system activated by an asphyxiant gas detection system. Reference: Tucson Fire Department Standard Operating Guideline for Compressed Gases dated 04/28/2015. |
| 04/13/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-1; FLOOR PLAN: PLEASE INDICATE ON THE DRAWINGS THE DISTANCE BETWEEN THE EXIT DOORS MEETS THE REQUIREMENTS OF THE IBC SECTION 1015.2.1. 2. SHEET A-1; FLOOR PLAN: PLEASE INDICATE ON THE PLAN THE MANEUVERING CLEARANCE AT THE ENTRY 101 MEETS THE REQUIREMENTS OF THE ICC/ANSI FIGURE 404.2.3.5(c) FOR BOTH DOORS. 3. GENERAL: PLEASE INDICATE ON A DRAWING EXITING AND THE ASSOCIATED EXIT TRAVEL DISTANCE. VERIFY THE REQUIREMENTS OF THE IBC SECTION 1016 ARE MET. 4. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS FOR THE IBC SECTION 1008.1.9.3 ARE MET FOR LOCKS AND LATCHES ON DOORS. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/20/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. What is item # 46 shown on the one line diagram and panel schedule for new panel 'K'. #2. The note on plan sheet E2 for IECC compliance does not exist in the 2012 IECC. Perhaps a typo. If sec. 101.4.3 exception #7 was intended as a reference. I don't that will apply because it appears that more than 50% lighting was added. Ref; 2012 IBC sec. 107.2.1, 2012 IECC, 2011 NEC. |