08/21/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/21/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
08/21/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/30/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
09/07/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E4.01. (a) Indicate feeder types (THWN, XHHW, etc) and material (copper or aluminum), and verify that they are sized per 310.15(B)(16) 75Deg column for the total load imposed on them. (b) Verify keyed note #10 at the generator does not correlate with the new feeder sizes shown below the generator diagram. The feeder indicating the 3/0 conductors is shown on the same line as the Monitoring Wiring. #2. Ref; All Site Plans. The site plan is shown 180 degrees in reference to the demo and new electrical work. Please clarify. Ref; 2012 IBC sec 107.2.1, 2011 NEC, |
09/11/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |