Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM02135
Parcel: 12404100A

Address:
930 E 2ND ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM02135
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2018 MARTIN BROWN FIRE REVIEW Approved
08/21/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/21/2018 ROBERT SHERRY WATER REVIEW Completed
08/30/2018 DAVID RIVERA ZONING REVIEW Approved
09/07/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E4.01.
(a) Indicate feeder types (THWN, XHHW, etc) and material (copper or aluminum), and verify that they are sized per 310.15(B)(16) 75Deg column for the total load imposed on them.
(b) Verify keyed note #10 at the generator does not correlate with the new feeder sizes shown below the generator diagram. The feeder indicating the 3/0 conductors is shown on the same line as the Monitoring Wiring.
#2. Ref; All Site Plans. The site plan is shown 180 degrees in reference to the demo and new electrical work. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC,
09/11/2018 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2018 SVALENZ1 OUT TO CUSTOMER Completed