Permit Number: T16CM02135
Parcel: 12404100A

Address:
930 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02135
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2016 MARTIN BROWN FIRE REVIEW Approved
04/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/08/2016 ROBERT SHERRY WATER REVIEW Passed
04/12/2016 STEVE SHIELDS ZONING REVIEW Approved
04/13/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A117S; ENLARGED SERVICE YARD PLAN: A DETAIL AT THE GATE JAMB NEEDS TO BE COMPLETED.
2. SHEET A117S; ENLARGED SERVICE YARD PLAN: PLEASE INDICATE A NORTH ARROW ON THIS PLAN.
3. SHEET A117S; ENLARGED SERVICE YARD PLAN: A DETAIL AT A MASONRY WALL NEEDS TO BE COMPLETED.
4. SHEET A117S; ENLARGED SERVICE YARD PLAN: A DETAIL AT A GATE POST INDICATES 15/A117. PLEASE REVISE.
5. SHEET A117S; ENLARGED SERVICE YARD PLAN: PLEASE INDICATE ELEVATION 15 ON THE PLAN.
6. SHEET S101: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SPECIAL INSPECTIONS.
7. SHEET S101; GENERAL STRUCTURAL NOTES (FOUNDATIONS): PLEASE PROVIDE ONE COPY OF THE SOIL REPORT FOR REVIEW.
8. SHEET S103; FOUNDATION PLAN: IT IS NOT CLEAR ON THIS PLAN WHERE THE GATE POSTS AND THEIR FOUNDATIONS ARE LOCATED. PLEASE CLARIFY ON THE PLAN.
9. SHEET S103; FOUNDATION PLAN KEYNOTES: NOTE 1 IS NOT INDICATED ON THE PLAN. PLEASE VERIFY.
10. SHEET S103; DETAIL 02: PLEASE INDICATE THE MASONRY WALL THICKNESS.
11. SHEET S103; GENERAL STRUCTURAL NOTES (FOUNDATIONS): PLEASE PROVIDE ONE COPY OF THE SOIL REPORT FOR REVIEW.
12. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/14/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2016 RBENT1 APPROVAL SHELF Completed
04/20/2016 RBENT1 OUT TO CUSTOMER Completed
04/20/2016 RBENT1 REJECT SHELF Completed