Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM02079
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/21/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 03/21/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | Re-stamped for Loren Makus by David Takaki 2/17/17 customer lost his plans |
| 03/21/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following eletrical plan review comments.Also provide a written response. #1. Provide complete compliance with the Tucson Outdoor Lighting Code. See section 104. #2. The light poles where modified to retro-fit new led fixture heads. Because of this modification and the use of the pole itself as a raceway, a third party NRTL will need to be performed to re- establish the listing as required per 2011 NEC art. 410.6. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/09/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |