Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM02062
Parcel: 12504142C

Address:
2228 E 1ST ST #1

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T16CM02062
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM02062
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. Show a complete roof detail with rafter ties (or ceiling joists) and collar ties (ridge straps) when the roof pitch is equal or greater than 3" to 12", R802.3. Update detail #5/6.
2. Show compliance with R802.3.1 with continuous ceiling joist and collar ties in the upper third of attic space. A ridge board may not be used without structural ties and straps.
3. Show rafter to wall connection using (H2.5) ties having a resistance to uplift of not less than 365 pounds on detail #5/6, R802.11.1. (City of Tucson Amended).

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 (R-30 with conditions) and walls R=13. Show the "R" values of insulation and the maximum "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2016 KROBLES1 OUT TO CUSTOMER Completed