Permit Number: T16CM02040
Parcel: 140420740

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM02040
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2016 MARTIN BROWN FIRE REVIEW Completed
04/06/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide for a special inspection for Outdoor Lighting Code Compliance as required per sec. 106.2.1 Tucson Outdoor Lighting Code.
#2. Ref: Plan sheet E-1.2. Detail 6 (Column J- Box Detail ) It appears there will be 480 volt cables installed inside the steel columns. The feeder schedule does not specify the type of cables. This would be a potential code violation per NEC art.300.27, unless the steel columns are listed as a raceway for conductors.
#3. Assign WARNING labels on all electrical equipment as required per NEC art. 690, 705.
#4. Please include conductor material ( CU- AL ) and insulation types on the feeder schedules or plan keynotes.
Ref: 2012 IBC 107.2.1, 2011 NEC
04/08/2016 STEVE SHIELDS ZONING REVIEW Passed
04/14/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S-1.0; GENERAL STRUCTURAL NOTES (FOUNDATIONS): NOTE 1 INDICATES A SOIL REPORT. PLEASE PROVIDE ONE COPY FOR REVIEW.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2016 ARUIZ1 OUT TO CUSTOMER Completed