| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2016 | MARTIN BROWN | FIRE | REVIEW | Completed | |
| 04/06/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide for a special inspection for Outdoor Lighting Code Compliance as required per sec. 106.2.1 Tucson Outdoor Lighting Code. #2. Ref: Plan sheet E-1.2. Detail 6 (Column J- Box Detail ) It appears there will be 480 volt cables installed inside the steel columns. The feeder schedule does not specify the type of cables. This would be a potential code violation per NEC art.300.27, unless the steel columns are listed as a raceway for conductors. #3. Assign WARNING labels on all electrical equipment as required per NEC art. 690, 705. #4. Please include conductor material ( CU- AL ) and insulation types on the feeder schedules or plan keynotes. Ref: 2012 IBC 107.2.1, 2011 NEC |
| 04/08/2016 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 04/14/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/19/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S-1.0; GENERAL STRUCTURAL NOTES (FOUNDATIONS): NOTE 1 INDICATES A SOIL REPORT. PLEASE PROVIDE ONE COPY FOR REVIEW. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/02/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |