Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T16CM02027
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 04/01/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G002; CODE ANALYSIS (ALLOWABLE HEIGHT): THE TABLE ON SHEET G002 FOR ALLOWABLE HEIGHT IS REFERENCED AS TABLE 504. PLEASE REVISE. 2. SHEET G002; CODE ANALYSIS (ALLOWABLE AREA): THE TABLE ON SHEET G002 INDICATES AN ALLOWABLE AREA THAT IS UNLIMITED PER THE IBC SECTION 507. IS THE SPECIFIC SECTION 507.3? IS THE BUILDING SURROUNDED AND ADJOINED BY PUBLIC WAYS OR YARDS NOT LESS THAT 60' IN WIDTH? PLEASE VERIFY. 3. SHEET G002; CODE ANALYSIS (HEIGHT/AREA INCREASE): WHY DOES THE TABLE ON SHEET G002 INDICATE THE HEIGHT AND AREA INCREASES ARE N/A? PLEASE CLARIFY. 4. SHEET G002; FIRE RESISTANCE RATING REQUIREMENTS: THE NOTE BELOW THIS TABLE REFERENCES TABLE 1017.1 FOR THE CORRIDOR FIRE RESISTANCE RATING. PLEASE REVISE THE TABLE REFERENCE. 5. SHEET G002; CODE ANALYSIS (PLUMBING FACILITIES): THE CODE REQUIREMENT FOR WATER CLOSETS IS LISTED AS 3 MEN AND 3 WOMEN, WHILE THE ACTUAL COUNT INDICATES 4 MEN AND 2 WOMEN. PLEASE VERIFY WHY THE CODE REQUIREMENT IS NOT MET. THE IBC SECTION 2902.1.1 (EXCEPTION) ALLOWS A WEIGHTED DISTRIBUTION OF THE SEXES WHERE APPROVED STATISTICAL DATA INDICATES SUCH. THIS WOULD REQUIRE A STATEMENT ON THE DRAWINGS BY THE ARCHITECT OF RECORD, CITING AN OWNER STATEMENT THAT SUCH A DISTRIBUTION OF THE SEXES IS THE NORM IN THIS FACILITY. 6. SHEET G004; PLAN: PLEASE INDICATE ON THE DRAWINGS THE ACCESSIBLE ENTRANCES, AND VERIFY THOSE ENTRANCES/EXITS MEET THE REQUIREMENTS OF THE IBC SECTION 1105. 7. SHEET A205; KEYNOTE FP14: PLEASE INDICATE IN THIS NOTE THE BOTTLE FILLER IS AN OPTION. 8. SHEET A205; KEYNOTES: NOTE FP09 REFERENCES DETAIL 10/A404 FOR THE ROOF ACCESS LADDER. PLEASE REVISE THE REFERENCE. 9. SHEET A508; PLAN 1: PLEASE VERIFY ON THE DRAWINGS (OR INCLUDE A REFERENCE) THE CROSS SLOPE OF THE RAMP MEETS THE REQUIREMENTS OF THE ICC/ANSI SECTION 405.3. 10. SHEET A601; ENLARGED PLAN 10: IN THE MEN'S ACCESSIBLE TOILET STALL, A KEYNOTE RR25 IS INDICATED. PLEASE FINISH THAT KEYNOTE IN THE LEGEND. 11. GENERAL (ARCHITECTURAL): THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE ALL SHEETS AS REQUIRED. 12. SHEET S0.1; GENERAL STRUCTURAL NOTES (DESIGN CRITERIA): THE FLAT ROOF SNOW LOAD MAY BE DESIGNED FOR 0 PSF, AND THE SEISMIC DESIGN CATEGORY MAY BE DESIGNED AS B. 13. SHEET S0.1; GENERAL STRUCTURAL NOTES (EARTHWORK): THE DESIGN CRITERIA LISTED ON THIS SHEET REFERENCES A SOIL REPORT THAT DOES NOT MATCH THE REPORT SUBMITTED. PLEASE CLARIFY AND REVISE THE SOIL BEARING PRESSURE, FROST PROTECTION, LATERAL EARTH PRESSURES, AND COEFFICIENT OF FRICTION. REVISE THE DESIGN CALCULATIONS AS REQUIRED. 14. SHEETS S1.1 AND S1.2: THE VERBIAGE FOR THE CONCRETE CLOSURE POUR CAN NOT BE READ ON THESE TWO SHEETS IN VARIOUS LOCATIONS. PLEASE REVISE. 15. SHEET S1.1; PLAN: BETWEEN GRIDS 5 AND 7 ON GRID B, AND BETWEEN GRIDS 6 AND 7 ON GRID D, SECTION CUTS 1/S1.3 AND 2/S1.3 ARE REVERSED. PLEASE REVISE. 16. SHEET S1.1 (PLAN); SHEET S1.4 (SECTION 6): THE SECTION IS CUT ON THE PLAN TO INCLUDE THE ADJACENT STEEL STAIR. PLEASE INCLUDE ON THE SECTION. 17. SHEET S1.2; PLAN: MOVE THE FLOOR SLAB NOTE INTO THE BOX. 18. SHEET S2.1; ELEVATION 1: PLEASE ADD A REFERENCE ON THIS ELEVATION FOR THE MASONRY LINTEL SCHEDULE. 19. STRUCTURAL CALCULATIONS; PAGE 8: THE DESIGN CRITERIA INDICATED HERE DO NOT MATCH THOSE INDICATED ON THE DRAWINGS. PLEASE COORDINATE AND REVISE THE DESIGN AS REQUIRED. 20. SHEETS S0.1 THROUGH S4.2: THESE SHEETS MUST BE STAMPED WITH AN ARIZONA REGISTRANT'S SEAL. 21. GENERAL (STRUCTURAL): THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE ALL SHEETS AS REQUIRED. 22. GENERAL (STRUCTURAL): PLEASE PROVIDE NORTH ARROWS ON ALL PLANS. 23. GENERAL (ARCHITECTURAL AND STRUCTURAL): THE GRID SYSTEM ON THE DRAWINGS TYPICALLY DOES NOT SHOW UP CLEARLY, ALONG WITH VARIOUS SECTIONS AND DETAILS. PLEASE DARKEN. 24. GENERAL; GEM SHEETS G0.00 THROUGH D3.2: PER THE IBC SECTION 107.3.4, THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL REVIEW AND COORDINATE SUBMITTAL DOCUMENTS PREPARED BY OTHERS. PLEASE FOLLOW THE IBC SECTION 107.3.4.1 TO INDICATE ON THESE DRAWINGS THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE HAS REVIEWED THESE DOCUMENTS AND FOUND THEM TO BE IN GENERAL CONFORMANCE TO THE DESIGN. 25. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/04/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a seal by an Arizona Registrant on the plumbing plans that is legible. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012. 3. Revise the detail of the water heater installation to include hot water recirculation. Reference: Sections 503 and 607.2, IPC 2012. 4. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012. 5. Clarify the waste and vent isometric, show the traps for the appropriate fixtures, and coordinate the location of the fixtures with the plumbing plans. Reference: Section 107.2.1, IBC 2012. 6. Verify the area of the parapet-enclosed roof used to determine the size of the roof drains; according to the architectural floor plans, that portion of the building has a projected roof area 4368 square feet. Include the effect of any vertical walls that can divert rainfall onto the roof in the calculations. Reference: Sections 1101, 1106 and 1108, IPC 2012. 7. Show the slope of the horizontal rainwater pipes on the plans. Reference: Section 1106.3, IPC 2012. 8. Clarify the termination of the roof drains and coordinate with the civil plans; no site storm drains are shown on the submitted civil drawings. Reference: Section 107.2.1, IBC 2012. 9. Southwest Gas, the local gas utility provides natural gas with an energy content of approximately 1,000 BTU per cubic foot. Reference: Section 402.1, IFGC 2012. |
| 04/04/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (typically installed directly after the water meter, outside of the building). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 04/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. |
| 04/05/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 04/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide NFRC fenestration product ratings for the U-factor and the SHGC values for the fenestration products shown on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. 2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 3. Clarify how excess outside air relief from the building is to be accomplished without recirculation of the relieved air into the building. Reference: Section C403.3.1.1.4, IECC 2012. 4. Show the size, routing, and termination of the condensate drains from the rooftop AC units and from the ductless AC unit. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 5. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. |
| 04/06/2016 | LMAKUS1 | ZONING | REVIEW | Needs Review | Development Package DP16-0046 must be approved first. |
| 04/06/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | Development Package DP16-0046 must be approved first. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/26/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |