Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM02023
Parcel: 113111180

Address:
1638 E SENECA ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T16CM02023
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2016 STEVE SHIELDS ZONING REVIEW Approved P&DS TRANSMITTAL


FROM: Steve Shields,
Lead Planner

PROJECT:
T16CM02023
1638 E. Seneca Street
Convert Garage to Sleeping Quarters

TRANSMITTAL: March 17, 2016


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 9'-0" the required perimeter to the west property line is 6'-0", proposed setback is 5'-1".
05/05/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
05/05/2016 ANDREW CONNOR NPPO REVIEW Passed
05/12/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed