Permit Number: T16CM02017
Parcel: 138244040

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM02017
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2016 FRODRIG2 BUILDING-COMMERCIAL REVIEW Approved
05/13/2016 ROBERT SHERRY WATER REVIEW Reqs Change Revise the water distribution system design criteria using the minimum daily service pressure, 47.6 PSI. Reference: Section 604.1, IPC 2012, as amended by the City of Tucson and Section A1.1, UPC 2012. [Initial comment: Tucson Water expects the water pressure range for this address to be 47.6 to 54.6 PSI.]
05/13/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/13/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/26/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved