Permit Number: T16CM01960
Parcel: 110035860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM01960
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 6; SHEET A1.1; FLOOR PLAN: THE MEASUREMENT INDICATED ON THE PLAN FOR EXIT ACCESS TRAVEL DISTANCE DOES NOT FOLLOW THE IBC SECTION 1016.3 (HORIZONTAL AND VERTICAL MEASUREMENTS ONLY). PLEASE REVISE ON THE PLAN AND VERIFY THE EXIT ACCESS TRAVEL DISTANCE IS 100 FEET OR LESS.
08/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed