Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01960
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 6; SHEET A1.1; FLOOR PLAN: THE MEASUREMENT INDICATED ON THE PLAN FOR EXIT ACCESS TRAVEL DISTANCE DOES NOT FOLLOW THE IBC SECTION 1016.3 (HORIZONTAL AND VERTICAL MEASUREMENTS ONLY). PLEASE REVISE ON THE PLAN AND VERIFY THE EXIT ACCESS TRAVEL DISTANCE IS 100 FEET OR LESS.
05/23/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The NFRC certification numbers (CPD#) have not been included in this submittal. Provide the NFRC certification numbers for the fenestration or provide a statement on the drawing that the fenestration submittals shall have maximum U-value and solar heat gain coefficients as shown on sheet A1.1 and they shall be NRFC certified. Reference: Section C303.1, IECC 2012. [Initial comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.]
05/23/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed