Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T16CM01894
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide scaled drawings - show how the design has been changed from the previously approved design. 2. Clarify the appliances being installed; provide equipment specifications. Why are the heat pumps being supplied with gas? 3. Show how the tankless water heater can be installed in the bathroom - Section 303.3, IFGC 2012. 4. Coordinate the gas piping schematic with the piping plan. Show how the gas piping that serves the appliances located on the second floor relates to the piping on the first floor. 5. Correct the addition for the total gas load. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/14/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 12/14/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 12/14/2017 | QJONES1 | REJECT SHELF | Completed |